Introduction

Brand: Erun

Name:On-line circulating cooling water quality analyser

Model: ERUN-SZ

Detection parameters: pH, dissolved oxygen, conductivity, turbidity, suspended solids, total hardness

ERUN-SZ series on-line circulating cooling water quality analyser,It is capable of comprehensively detecting a number of water quality parameters including pH, dissolved oxygen content, conductivity, turbidity, suspended solids concentration, total hardness, chloride ion content, total iron content, copper ion concentration, oil content, free chlorine concentration, NH3-N concentration and chemical oxygen demand (COD).In addition, the analyser supports optional detection of parameters such as full alkalinity and silica to meet a wider range of needs.

It has a wide range of applications covering steelmaking, ammonia production, thermal power plants, foundry industry, steel rolling production, blast furnace and converter operations, petroleum refining and other industries, and is suitable for continuous and real-time on-line monitoring and analysis of a variety of circulating cooling water systems, such as inter-cooled open-ended circulating cooling water, direct-cooled open-ended circulating cooling water, as well as inter-cooled closed-ended circulating cooling water, and other circulating cooling water systems.

Parameters

Online circulating cooling water quality analyser product parameters:

parametric

range

resolution

precision error

pH

-2.00~16.00

0.01

±0.02

dissolved oxygen(DO)

0~200.0 ug/L

0~20.00 mg/L

0.1ug/L

0.01mg/L

±1.0%F.S.

conductivity

0~20.00μS/cm;

0~200.0μS/cm;

0~2000μS/cm;

0~20.00mS/cm

0.01μS/cm

0.1μS/cm

1μS/cm

10μS/cm(0.01 mS/cm)

±2.0%(F.S.)

turbidity

0-200NTU

(flow-through)

0.001NTU

±2%F.S.

suspension

0-500mg/L

(flow-through)

1mg/L

±2%F.S.

total hardness

0-500mg/L

0.01mg/L

±5%F.S.

chloride ion

0-2000mg/L

0.01mg/L

±5%F.S.

total iron

0-10mg/L

0.01mg/L

±10%

copper ion

0-2/5/10mg/L

0.01mg/L

±5%

oil

0-50ppm

0.01ppm

R2>0.999

free chlorine

0-20.00mg/L

0.001mg/L

±1%F.S.

NH3-N

0-100mg/L

0.01mg/L

±10% or ±0.5 mg/L

COD

0-500mg/L

0.01mg/L

±5%

full alkalinity

0-200/500/1000mg/L

0.001mg/L

±10%

silicon dioxide (SiO2)

0-2000µg/L

0.01µg/L

±2.5%F.S.

Features

On-line circulating cooling water quality analyser Product Features:

Detection method:

Fixed installation, sampling line/insertion type online monitoring

Display:

The transmitter display shows the concentration value in real time and can be integrated with a 7" LCD touch screen with LED backlighting.

Working power supply:

AC220V、50/60HZ

Data Transfer:

RS 485 (Modbus RTU), 4-20mA, relay output, etc., optional wireless transmission module + ERUN cloud platform

Data storage:

Historical data can be queried, support for U-disk export

Storage Interval:

1-3600s can be set, default 10s

Inlet pressure:

1-2 bar (pressure reducing valve is recommended for high pressure)

Water velocity:

300-500mL/min

Ambient temperature:

0-50℃

Water sample temperature:

0-40℃

Inlet/outlet connections:

6mm/10mm hose

Protective features:

IP68 for sensor electrodes, IP65 for transmitters/total integrated cabinet

+86 18166600151