PH(25℃) | conductivity(25℃) μS/cm | copper content (CU)μg/L | dissolved oxygen (DO)μg/L |
8.0-9.0 | 0.4-0.2 | ≤20 | - |
7.0-9.0 | ≤30 |
PH(25℃) | conductivity(25℃) μS/cm | copper content μg/L |
expected value:8.0-9.0 | <5 | ≤40 |
standard value:7.0-9.0 |
PH(25℃) | conductivity(25℃) μS/cm |
6.5-7.5 | 0.5-1.2 |
serial number | model number | name | Detection range | photograph |
1 | ERUN-ST3-PL | Benchtop Touch Screen PH Acid Meter | -2.000-18.000 pH | |
2 | ERUN-ST3-A4 | Touch screen micro conductivity tester | 0.0000~2.0000)μS/cm and(0.000~20.000)μS/cm | |
3 | ERUN-ST3-H6 | Trace Copper(Cu) Content Analyser | (0.0~200.0)μg/L | |
4 | ERUN-SP3-A5 | Micro Dissolved Oxygen (DO) Analyser | 0-100μg/L |
In summary, generator cooling water quality testing is an important part of ensuring the stable operation of the power generation system.By choosing appropriate testing methods, conducting regular water quality testing and taking corresponding treatment measures, the normal operation of the generator can be effectively guaranteed and its service life can be extended.